Power & Energy Converter Power · Energy

Power, energy, and the time that links them — convert any unit to every other, bridge power and energy through a duration, and size a boiler against its burner.

Pick any power or energy unit — every equivalent in that dimension updates live. To turn power into energy (or back), use the Power × Time = Energy tab.

UnitValue
W watt
kW kilowatt
MW megawatt
BTU/hr BTU per hour
MBH thousand BTU/hr
MMBtu/hr million BTU/hr
ton refrigeration
hp horsepower
boiler hp boiler horsepower
kcal/hr kilocalorie/hr
J joule
kJ kilojoule
MJ megajoule
GJ gigajoule
Wh watt-hour
kWh kilowatt-hour
MWh megawatt-hour
BTU British thermal unit
kBtu thousand BTU
MMBtu million BTU
therm 100,000 BTU
kcal kilocalorie
Energy
Also

Riello notation is min / high-low ÷ high-high (the ÷ is European “to”). Pasting it fills the burner fields above and decodes the adjustable high-fire band — the firing diagram and the commissioned high-fire setting are authoritative.

Effective turndown
Min fire % of input
Plant input (total)
Burner turndown
Decoded firing

M is the Roman thousand, not mega. In HVAC, MBH = MBtu/hr = MBtuh all mean thousand BTU/hr, while MMBtu means million BTU. Reading an “MBtu” as a million (or an “MMBtu” as a thousand) is a 1000× error — this tool labels both explicitly and parses MBH / MBtu/hr as the same unit.

1 of…equals
kW3.412 MBH = 0.2843 ton = 1.341 hp
ton (refrig.)12 MBH = 3.517 kW = 4.72 hp
hp0.7457 kW = 2.544 MBH
boiler hp33.47 MBH = 9.81 kW = 0.0335 MMBtu/hr
MMBtu/hr1,000 MBH = 293.1 kW
therm100,000 BTU = 29.31 kWh = 0.1 MMBtu
kWh3,412 BTU = 3.6 MJ
MMBtu293.1 kWh = 1,055 MJ = 10 therms

Worked example (the service call that prompted this tool): a 167 kW boiler is 570 MBH; an 835 MBH-input boiler fired down to a 570 MBH burner minimum gives 835 ÷ 570 ≈ 1.46:1 turndown — poor, and a predictor of short-cycling. Match the burner output to the boiler input (fuel fired), not its gross output, and multiply per-boiler ratings by quantity for plant totals.