Field Electrical Quick Calc Electrical

The bread-and-butter electrical math you double-check on a service call, in one place. Ohm’s Law & Power is the wheel — type any two of V / I / R / P and it solves the other two. AC Power ties line voltage, amps, kW, kVA, kVAR, and power factor together for single- and three-phase. Motor HP / kW / FLA converts horsepower to kilowatts and estimates full-load amps. Voltage Imbalance runs the NEMA check on three line-to-line readings.

Enter exactly two — the other two are solved and shown in blue. DC or resistive loads (PF = 1); for motors and reactive loads use the AC Power tab.

Voltage (V)
Current (I)
Resistance (R)
Power (P)
Solve forFrom the other two
V (volts)I·R  ·  P/I  ·  √(P·R)
I (amps)V/R  ·  P/V  ·  √(P/R)
R (ohms)V/I  ·  V²/P  ·  P/I²
P (watts)V·I  ·  I²·R  ·  V²/R

Worked example: a relay coil measures R = 4 Ω and the panel feeds it V = 12 V.

  1. I = V/R = 12 ÷ 4 = 3 A
  2. P = V²/R = 144 ÷ 4 = 36 W

So the coil draws 3 A and burns 36 W — sanity-check that against the coil’s wattage rating before you trust the circuit.

Line voltage is line-to-line — 208 / 240 / 480, not 120 / 277. Three-phase carries the √3 factor; pick 1φ for a line-to-neutral branch.

Line current Iₗ
Real power
Apparent power
Reactive power
Phase angle θ

Q is a magnitude; lagging (inductive) is assumed. Size conductors and breakers on amps (kVA-derived), not on kW.

PFAngle θkW / kVA
1.000.0°1.00
0.9518.2°0.95
0.9025.8°0.90
0.8531.8°0.85
0.8036.9°0.80

Worked example (3φ): a 460 V supply fan pulls 30 A at PF 0.85, three-phase.

  1. S = √3 × 460 × 30 = 23.90 kVA (apparent)
  2. P = S × 0.85 = 20.32 kW (real)
  3. Q = √(S² − P²) = 12.59 kVAR (reactive), θ = acos 0.85 = 31.8°

Line-to-line and line-to-neutral differ by √3 (VLL = √3 × VLN) — a 480 V system reads 277 V to neutral. Enter the L-L value here.

PF and η are your assumptions — edit them to the nameplate when you have it. Efficiency takes 0.90 or 90.

HP ↔ kW
Estimated full-load amps
Estimate only — not a code value. Computed from your stated PF and efficiency, this reads roughly 10–25 % low versus the NEC tables (the gap widens below 5 HP). Size motor conductors, branch-circuit protection, and disconnects off the table FLC — NEC 430.250 (3φ) / 430.248 (1φ) — never this number. Overload protection (430.32) uses the nameplate FLA.
Enter a measured clamp reading to compare against the estimate.
Motor HP3φ @ 460 V (A)1φ @ 230 V (A)
12.18
23.412
34.817
57.628
7.51140
101450
1521
2027
2534
3040
5065

Worked example: a 10 HP, 460 V, three-phase motor at PF 0.88 and η 0.90.

  1. FLA = (10 × 746) / (√3 × 460 × 0.88 × 0.90) = 7460 ÷ 631 = 11.8 A — the estimate.
  2. NEC 430.250 lists 14 A for this motor — about 16 % higher.

That gap is the whole point: the table builds in a representative low PF and efficiency, so it always runs higher than your stated-PF estimate. Size off the 14 A table value, never the 11.8 A estimate.

Measure all three phase-to-phase legs at the motor terminals with the load running. NEMA defines unbalance as the largest deviation from the average, over the average.

Average voltage
Max deviation
Voltage unbalance
Enter the three readings to see the verdict.
UnbalanceWhat it means
≤ 1 %Acceptable — no derate.
1 – 5 %Derate the motor per the NEMA curve; find and fix the cause.
> 5 %Do not operate — correct the supply first.

Worked example: a motor reads 460 / 455 / 450 V across its three legs.

  1. avg = (460 + 455 + 450) ÷ 3 = 455 V
  2. max deviation = |460 − 455| = 5 V
  3. unbalance = 5 ÷ 455 × 100 = 1.10 % — just into derate territory.

Voltage unbalance is brutal at the motor: the current unbalance runs roughly 6–10× the voltage unbalance, and the extra current is pure heat in the windings. Chase a 1 % reading to a loose lug, an unbalanced single-phase load on the feeder, or the utility.

← All tools