Economizer Ratio Helper HVAC
How far do I open the outdoor-air damper to hit a mixed-air setpoint at these conditions?
Inputs are seeded with an example — edit them to your numbers.
Input
Output
Worked example
Summer cooling on an economizer-favorable morning — OA 60 °F, RA 75 °F, mixed-air setpoint 65 °F.
- Setpoint sits between OA and RA → feasible.
- The damper has to bring in enough OA to drag the mix down to setpoint:
% OA = (MA − RA) ÷ (OA − RA) × 100 - Plug in:
(65 − 75) ÷ (60 − 75) × 100 = 66.7 %. - Two-thirds outdoor air, one-third return — that's the damper command.
When the calc lands between 0 and 100 %, that's the damper
command. Outside that band the mix is physically impossible,
so the readout blanks to — and the feasibility
line carries the why: below 0 % means OA is hotter than the
setpoint AND than the room — minimum-OA only, no economizer;
above 100 % means OA is cooler than the setpoint but not cold
enough to carry the whole load alone (drop the setpoint to
55 °F to
see it — the damper goes wide open and the coil makes up the
rest).
Input
Outdoor air
Return air
Mixed-air target
Atmospheric pressure fixed at sea level for v1; humidity and enthalpy match the chart tool at 0 ft altitude. Open the chart tool if you need an altitude-adjusted answer.
Output
Resulting mixed-air state
Enthalpy changeover
Worked example
Mild-but-muggy morning — OA 78 °F / 68 °F WB, RA 75 °F / 63 °F WB, MA setpoint 65 °F.
- Dry-bulb is what the damper modulates to.
% OA = (65 − 75) ÷ (78 − 75) × 100= a negative number — OA is hotter than RA, so even on dry-bulb alone the economizer can't help. Minimum-OA position. - The mixed-state readouts show what the coil would see at the calc's %OA — useful when the answer lands between 0 and 100.
- The enthalpy comparison is the real reason a high-end BAS is more conservative: an OA that's two degrees cooler than RA but soaked with moisture carries more heat per pound than RA does. Free cooling on dry-bulb alone, latent penalty on the coil.
Most commercial economizer logic is dry-bulb with a
humidity high-limit; enthalpy economizer logic
compares hOA vs.
hRA to gate the damper before
any dry-bulb modulation runs.
A %OA answer is a setpoint theory, not a safe command. Use it to check whether a sequence’s arithmetic holds together and to learn the changeover logic — then let the low-limit protections decide how far the dampers actually open. In cold weather the same math that finds free cooling can call for enough outdoor air to freeze a coil; the freezestat and the mixed-air low limit govern, not the calculator.